Spesifikasi TSI ALNOR EBT731-STA Balometer Capture Hood
Alat Uji Kualitas Air
AIR QUALITY MONITOR
The TSI Alnor EBT731 Balometer® Capture Hood is a multipurpose electronic air balancing instrument primarily used for efficiently taking direct air volume readings at diffusers and grilles. It features a detachable micromanometer which can be used with optional probes for increased flexibility in multiple measurement applications. The EBT731 also includes Bluetooth communications for transferring data or remote polling. LogDat Mobile provides a wireless interface to TSI instruments via Bluetooth. Click LogDat Mobile for more details
Offering durable, trouble-free operation, this lightweight, ergonomically designed capture hood kit saves time and money by combining multiple measurement tools into one package. The EBT731 Balometer® Capture Hood helps you create healthy and energy efficient environments while meeting local codes, guidelines and regulations for ventilation systems.
Applications include:
Test and balance contractors
Commissioning agents
Facilities managers
Health and safety specialists
Ventilation system installers
Features
Automatically senses and displays supply or return flows
Back pressure compensation ensures accurate readings
Multiple hood sizes available
Bluetooth communications
Detachable digital micromanometer offers flexibility
Includes 2 ft x 2 ft (610 mm x 610 mm) air capture hood/frame/base
Velocity
Pitot probes: 25 to 15,500 ft/min
Air flow probe: 25 to 5,000 ft/min
Velocity matrix: 25 to 2,500 ft/min
Accuracy: ±3% of reading ±7 ft/min
Pressure
Differential pressure: ±15in H2O
Absolute pressure: 15 to 40 in Hg
Accuracy: ±2% of reading
Volume
Range: 25 to 2,500 ft3/min capture hood
Accuracy: ±3% of reading
Relative humidity
Range: 5 to 95% RH
Accuracy: ±3% RH
Temperature
Sensor in base: 40 to 140°F
Temperature/RH probe: 14 to 140°F (optional accessory)
Accuracy: ±0.5°F
NIST Certificate Included
Meets performance guidelines as outlined under the 2013 California Building Efficiency Standards (Title 24, Part 6) Section 100.0 (h), residential Appendices Section RA3.3.2.1 and RA3.7.3
What's in the Box
2 x 2ft (610 x 610mm) air capture hood/frame/base
Detachable micromanometer
18 inch (46cm) pitot prob
2 static pressure probes
16ft (4.8m) neoprene tubing
Wheeled luggage-style carrying case
NIST-traceable calibration certification
4 AA size rechargeable NiMH batteries
Multi-country AC adapter
Downloading software
USB interface cable
Manual